EELT7030 — Operation and Expansion Planning of Electric Power Systems
Federal University of Paraná (UFPR)
Module: Transmission Line — Constraints
Author
------
Augusto Mathias Adams <augusto.adams@ufpr.br>
Description
-----------
Defines the physical and operational constraints for transmission
lines in DC power flow formulations. These constraints link line
flows to phase-angle differences through susceptance and limit
the flow magnitude according to each line’s capacity.
Functions
---------
add_transmission_line_flow_constraints(m)
Enforce the DC flow definition:
``F_ij,t = b_ij (θ_i,t − θ_j,t)`` for all lines and time periods.
add_transmission_line_flow_limits_constraints(m)
Apply the flow capacity limits:
``−pmax_ij ≤ F_ij,t ≤ pmax_ij`` for all lines and time periods.
Notes
-----
- Each line is characterized by:
- ``b_ij`` : susceptance (1/x_ij)
- ``pmax_ij`` : maximum active power flow (MW)
- ``endpoints`` : list of two bars [i, j]
- These constraints are suitable for both static (operational)
and mixed-integer (expansion) formulations.
- Phase angles ``θ_i,t`` and ``θ_j,t`` must exist in the model
before these constraints are declared.
References
----------
[1] CEPEL, DECOMP / DESSEM. Manuais de Metodologia, 2023.
[2] Unsihuay Vila, C. Introdução aos Sistemas de Energia Elétrica,
Lecture Notes, EELT7030/UFPR, 2023.
"""
from pyomo.environ import Constraint, ConcreteModel
[docs]
def add_transmission_line_flow_constraints(m: ConcreteModel) -> ConcreteModel:
"""
Add DC flow definition constraints to the model.
Enforces, for each line ``l`` and time period ``t``:
``F_ij,t = b_ij (θ_i,t − θ_j,t)``
For the transport model, F_ij,t is unrestricted by Second Kirchoff law
Parameters
----------
m : pyomo.environ.ConcreteModel
Pyomo model containing:
- ``m.LT`` : set of transmission lines
- ``m.T`` : set of time periods
- ``m.lines_flow[l,t]`` : power flow variable (MW)
- ``m.lines_b[l]`` : line susceptance (1/x)
- ``m.lines_endpoints[l]`` : list of bar identifiers [i, j]
- ``m.theta[b,t]`` : phase angle variable (radians)
Returns
-------
pyomo.environ.ConcreteModel
The same model with constraint block ``m.FlowDefinitionConstraint``.
Notes
-----
- Flow sign convention: positive from the first to the second
bar in the ``endpoints`` list.
- This constraint establishes the physical relationship between
electrical angles and transmitted power in the DC approximation.
"""
def _flow_rule(m, l, t):
i, j = m.lines_endpoints[l]
if m.lines_transmission_model[l] == "dc":
# trick to get Power Flow in MW => multiply by p_base
return m.lines_flow[l, t] == m.p_base * m.lines_b[l] * (m.theta[i, t] - m.theta[j, t])
return Constraint.Skip
m.FlowDefinitionConstraint = Constraint(m.LT, m.T, rule=_flow_rule)
return m
[docs]
def add_transmission_line_flow_limits_constraints(m: ConcreteModel) -> ConcreteModel:
"""
Add flow capacity limit constraints to the model.
For each line ``l`` and time period ``t``:
``−pmax_ij ≤ F_ij,t ≤ pmax_ij``
Parameters
----------
m : pyomo.environ.ConcreteModel
Pyomo model containing:
- ``m.LT`` : set of transmission lines
- ``m.T`` : set of time periods
- ``m.lines_flow[l,t]`` : power flow variable (MW)
- ``m.lines_pmax[l]`` : maximum capacity (MW)
Returns
-------
pyomo.environ.ConcreteModel
The same model with constraint block ``m.LinesFlowMaxLimitConstraint`` and
``m.LinesFlowMinLimitConstraint``.
Notes
-----
- The limit is symmetric (±pmax) and applies to both flow directions.
- These constraints should be added after
:func:`add_transmission_line_flow_constraints`.
"""
def _flow_max_rule(m, l, t):
return m.lines_flow[l, t] <= m.lines_pmax[l]
def _flow_min_rule(m, l, t):
return m.lines_flow[l, t] >= - m.lines_pmax[l]
m.LinesFlowMaxLimitConstraint = Constraint(m.LT, m.T, rule=_flow_max_rule)
m.LinesFlowMinLimitConstraint = Constraint(m.LT, m.T, rule=_flow_min_rule)
return m